0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz

Product Details
Customization: Available
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Diamond Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Fast Delivery
The supplier can deliver the goods within 30 days
In-stock Capacity
The supplier has In-stock capacity
to see all verified strength labels (26)
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
  • 0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
Find Similar Products
  • Overview
  • Product Description
  • Company Profile
  • FAQ
Overview

Basic Info.

Model NO.
SJKCPS-45C
Speed
Normal Type Circuit Breaker
Arc-extinguishing Medium
Air
Installation
Fixed
Structure
Cps
Poles Number
3,4p
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), Short-Circuit.Overload Phase Failure .Earth Leakag
Certification
ISO9001-2000, CE, CCC
Product Type
Motor Protection Switch (MPCB)
Rated Voltage
AC380V
Level of Protection
IP65
Protection Function
Overload / Short Circuit / Phase Loss / Locked Rot
Applicable Motor Powe
0.5-30kw
Response Time
<2s(Overload)
Reset Method
Manual Reset
Operating Temperature
-20ºC ~ +60ºC
Certification Standards
CE, ISO 9001
Intelligent Function
APP-Based Remote Control
Transport Package
Box
Trademark
JCHKO
Origin
Zhejiang, China
HS Code
8536200000
Production Capacity
5000 Pieces/Week

Product Description

Product Description
0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
SJKCPS Control and Protective Switching device
The SJKCPS Control and Protective Switching Device (CPS) is an integrated electrical protection and control solution designed for industrial and commercial applications. It operates in AC 50/60Hz systems with rated voltage up to 400V and a wide current range from 1A to 125A, providing reliable performance for motor and circuit management under both normal and fault conditions.
Key Features
     - Integrated Control and Protection: Combines multiple functions in one compact device.
     - Wide Current Range: Supports 0.16A to 100A for versatile applications.
     - High Reliability: Designed for continuous operation with long electrical and mechanical life.
     - Modular and Compact: Space-saving structure with high protection against environmental factors.
     - Easy Installation and Maintenance: User-friendly design simplifies operation and servicing.
Technical Specifications
Model:                          SJKCPS
Rated Current:             1A - 125A
Rated Voltage:             Up to 400V AC
Frequency:                   50Hz / 60Hz
Breaking Capacity:      High (IEC compliant)
Protection Level:         High resistance to pollution and arcs
 Type Designation
 SJKCPS               /                  /                               
        1             2       3           4       5           6       7       8       9
1
Control and Protection Switching Device
2
Main Frame Current Rating (45,125)
3
Breaking Capacity Code: C-Economic Type; Y-standard Type; H-High Type
4
Load Type (Motor M/Power Distribution P)
5
Rated Current (1A~125A)
6
Accessories (02,06, 09)(unmarked if not present)
7
Coil Control Voltage (M: AC230V; Q: AC400V)
8
Basic Type (unmarked); F-Fire Protection Type (alarm only, no tripping)
9
G- Isolated Type (unmarked if not present)

Technical Parameters
Frame Current
IthA
Main Rated Current
InA
Overload Electronic Trip Rated Current Ie (A)
Overload Electronic Trip Current Adjustment Range
80V Control Power Range (kW)
Utilization Category
Rated Voltage (V)
Rated Frequency (Hz)
45
SJKCPS-16
1
0.4~1
0.12~0.33
AC-42
AC-43
AC-44
380(400)
50(60)
3
1.2~3
0.5~1.5
6
2.4~6
1.5~3
10
4~10
2.5~5
16
6.4~16
4.5~7.5
SJKCPS-32
25
10~25
5.5~11
32
13~32
11~15
SJKCPS-45
45
18~45
15~22
125
SJKCPS-63
63
25~63
18.5~30
SJKCPS-80
80
32~80
30~37
SJKCPS-100
100
40~100
37~45
SJKCPS-125
125
50~125
40~55
Operating Characteristics for Motor Control (Utilization Categories: AC-42, AC-43, AC-44)
Motor Control Operating Characteristics
No.
Multiple of rated current (In)
Conventional Time Related to Ie (h)
Reference Temperature
1
1.0
No tripping within 2h
+20℃
2
1.2
Tripping within 2h
3
1.5
Tripping within 4min
4
7.2
Tripping within 4-10s
Thermal Trip Characteristics for Power Distribution Loads (Utilization Categories: AC-40, AC-41)
Power Distribution Characteristics
Utilization Category
Multiples of Set Current (Ir1)
Conventional Time Related to Ie (h)
Reference Temperature
A1)
B2)
le<63A
le≥63A
AC-40
1.05
1.3
1
2
+30℃
AC-41
Notes:
A: When applying A times set current to all poles, no tripping occurs within conventional time.
B: When subsequently applying B times set current, tripping shall occur within conventional
Product Utilization Categories and Typical Applications
Circuit
Utilization Category
Typical Applications
Main Circuit
AC-20A
Connecting and disconnecting circuits without conditions
AC-40
Power distribution circuits, including mixed resistive and inductive loads with reactors
AC-41
Non-inductive or slightly inductive loads, resistance furnaces
AC-42
Slip-ring motors: starting, breaking
AC-43
Squirrel-cage induction motors: starting, breaking during operation
AC-44
Squirrel-cage induction motors: starting, plugging/reversing, jogging
AC-45a
Switching discharge lamps
AC-45b
Switching incandescent lamps
Circuit
Utilization Category
Typical Applications
Auxiliary Circuit
AC-15
Controlling AC electromagnetic loads
AC-20A
Connecting and disconnecting circuits without conditions
AC-21A
Switching resistive loads, including appropriate overloads
DC-13
Controlling DC electromagnetic loads
DC-20A
Connecting and disconnecting circuits without conditions
DC-21A
Switching resistive loads, including appropriate overloads
SJKCPS System vs Discrete Components Comparison
No.
Technical Performance
Discrete Components
SJKCPS
1
Breaking Capacity
10-50KA
35-80kA
2
Mechanical Life
500-1000 million operations
500-1000 million operations
3
Electrical Life
10-15 million operations
10-15 million operations
4
Current Setting Adjustment
Curve
Linear
5
Circuit Matching Consistency
Poor
Good
6
Current Limiting Capability
Low
High
7
Self-protection Features
None
Available
8
Continuous Operation Characteristics
None
Available
Current and Cable Specifications
Operating Current Range (A)
Conductor Cross-section (mm²)
0<l<8
1.5
8<l<12
2.5
12<I<20
4
20<I<25
6
25<I<50
10
50<l<63
16
63<I<100
25
Common Fault Problems and Troubleshooting Methods
No.
Fault Phenomenon
Fault Cause
Solution
1
Power on, SJKCPS not working
1. Check if operation knob is in "AUTO" position
2. Verify A1, A2 control power supply
Turn knob to "AUTO" position
Connect control power correctly
2
Power on, SJKCPS coil burned
Check if A1, A2 control power is wrongly connected or short-circuited
Replace SJKCPS coil or check control circuit
3
SJKCPS switch not self-locking
1. Auxiliary contacts 13, 14
2. Check if A1, A2 control voltage too low
If contacts don't conduct when closed, replace accessory or check control circuit
4
SJKCPS closed but motor not working
Check 3-phase power supply
Connect correct 3-phase power
5
Motor starts but SJKCPS trips
1. Check if 05, 08 short-circuit contacts closed
2. Verify if 95, 98 overload contacts conduct
3. Check if both fault contacts (05,08 and 95,98) closed
1. Short circuit in load circuit
2. Verify load matches SJKCPS rating
6
Load runs for while then SJKCPS trips
SJKCPS intelligent trip unit protection
1. Run SJKCPS without load
2. Press shift key for fault query
3. LED shows fault reason (last 3 faults)
4. Troubleshoot based on displayed fault type
7
Motor burned but SJKCPS didn't trip
Incorrect parameter settings (Ie etc.)
Reset SJKCPS parameters according to actual load
0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
Company Profile
0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
0169 Sjkcps-45c Multi-Function Control and Protection Switch 50Hz
FAQ
Could I have prices of your produets?
Welcome. Pls feel free to send us an email here.You will get our reply in 24 hours.
Can we print our logo/webiste/company name on products?
Yes, please advise the size and Pantone Code of the logo.
What's the lead time for regular order?
7-15 days for order quantity Iower than 1000pc;For more quantity,usualy 20 days.
Do you inspect the finished products?
Yes,each step of production and fnished products will be came out inspection by QC department before shipping.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now