Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1 | Number of poles: 4-pole marked as 4,no marking for 3-pole |
2 | Rated current of circuit breaker frame level |
3 | Design serial number |
4 | Jniversal circuit breaker |
5 | Enterprise code |
Circuit Breaker Operating Characteristics The operating characteristics of circuit breakers are expressed by number of operating cycles | |||||||
Rated Current of Frame Level(A) | Total Number of Operating Cycles | ||||||
1600,2000 | 10000 | ||||||
3200, 4000 | 5000 | ||||||
6300 | 2000 | ||||||
Operating Voltages and Power Requirements for Shunt Release, Undervoltage Release, Motorized Operating Mechanism, Closing Electromagnet, and Intelligent Controller | |||||||
Rated Operating Voltage Item Power Required | AC(50Hz) | DC | |||||
220V | 380V | 110V | 220V | ||||
Shunt Release | 24VA | 36VA | 24VA | 24VA | |||
Undervoltage Release | 24VA | 36VA | |||||
Closing Electromagnet | 24VA | 36VA | 24VA | 24VA | |||
Motorized Operating Mechanism | Circuit Breaker Frame Level Rated Current | 2000A | 85VA | 85VA | 85VA | 85VA | |
3200A, 4000A | 110VA | 110VA | 110VA | 110VA | |||
6300A | 150VA | 150VA | 150VA | 150VA | |||
Intelligent Controller Power Supply Voltage | AC220V, AC380V, DC220V, DC110V | ||||||
Note: The reliable operating voltage range is 70%-110% for shunt release, and 80%-110% for closing electromagnet and operating mechanism. |
Technical Data and Performance · Rated Current of Circuit Breaker | ||||||
Rated Current of Frame Level (InmA) | Rated Current (In A) | |||||
1600 | 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 | |||||
2000 | 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000 | |||||
3200 | 2000, 2500, 2900, 3200 | |||||
4000 | 3200, 3600, 4000 | |||||
6300 | 4000, 5000, 6300 | |||||
· Rated Short-circuit Breaking Capacity & Short-time Withstand Current, With "Zero" Arc Distance (No External Arcing) | ||||||
Rated Current Level (InmA) | 2000 | 3200 | 4000 | 6300 | ||
Ultimate Short-circuit Breaking Capacity Icu(kA)O-Co | 400V 690V | 80 | 100 | 100 | 120 | |
50 | 65 | 65 | 80 | |||
Rated Short-circuit Making Capacity nxlcu(kA)/cosφ | 400V 690V | 176/0.2 | 220/0.2 | 220/0.2 | 264/0.2 | |
105/0.25 | 143/0.2 | 143/0.2 | 187/0.2 | |||
Service Short-circuit Breaking Capacity Ics(kA)O-CO-CO | 400V 690V | 50 | 65 | 80 | 100 | |
40 | 50 | 65 | 80 | |||
Rated Short-time Withstand Current Icw(kA)1s,Time Delay 0.4s,O-Co | 400V 690V | 50 | 65 | 65/80(MCR) | 85/100(MCR) | |
40 | 50 | 50/65(MCR) | 65/75(MCR) | |||
Note: Breaking capacities are identical for both top and bottom cable entry |
Packaging | Please contact us! |